Experion LX

Honeywell Process Solutions
Experion LX
Category: Host
Revision: R120.1
Type: Class 61b Integrated Host System
Host Registration Date: February 2, 2015
Test Campaign Number: HP100500
Tester Version: 2.2
Test Status: Registered
 
Stack
Manufacturer (H1): Softing AG
Revision (H1): 1.60
Test Campaign Number (H1): CT0168FF
Manufacturer (HSE): NA
Revision (HSE): NA
Test Campaign Number (HSE): NA
 
Physical Layer
Physical Layer types: 114 - Standard-power signaling, separately powered, non I.S.
Test Campaign Number: PT-307 (Series B FIM 4)
PT-507 (Series C FIM 4)
 
Foundation Host Profile Details
Foundation Host Profile: Class 61b Integrated Host
Additional FOUNDATION Host Profiles:
Click to view Other Profiles
Host Interface Type Supported: H1 Interface
Communication Profile Class: 31PS, 32L
 
Host ProfileSupported Features
H1 Device Support: H1 Device Address Assignment
Configuration of Link Master Devices
H1 Physical Device Tag Assignment
Convert Link Master to Basic Device
H1 Software Download
HSE Support: Not Supported
Distributed Application Support: Block Tag Configuration
Block Instantiation
Multiple Capability Levels
Resource and Transducer Blocks
Standard Function Blocks
Enhanced Function Blocks
Profiled Custom Function Blocks
Custom Function Blocks
Configuration of scheduled control function blocks
Function Block Linking and Publication Scheduling
Function Block Execution Scheduling
Alert Configuration and Handling: Process Alert Management Configuration
Process Alert Handling and Confirmation
Device Alert Management Configuration
Device Alert Handling and Confirmation
Multi-bit Alert Support
Device Description Support: DD Blocks and Parameters
DD v4 Methods execution
DD v4 Menus
DD v5 Visualizations, Methods
DD v5 Persistent data
DD v5.1 Device-Level Access
Capability File Support
Data Quality Support: Not Supported
 
System Components:
System Components: C300 controller - R120.1

Fieldbus Interface Module 4 links(FIM4) - R120.1

Control Builder - R120.1

Experion Server - R120.1

Experion Station - R120.1
 
Previous Registrations
Previous Revisions:
Click to view Previous Versions
More Information:

Experion LX is an extension of Honeywell’s award-winning Experion Process Knowledge System (PKS) built to effectively manage continuous process control and optimize batch and sequence-oriented applications for a wide range of processes. It leverages Honeywell’s track record as a recognized leader in process control technology with innovative design of Series 8 I/O modules, validated wider range of Commercial off the Shelf (COTS) options, easy engineering and maintenance capabilities, and integrator-friendly programs and tools. Experion LX is a highly reliable and scalable control platform for customers to increase their profitability and productivity and accessibility to local support without sacrificing quality and reliability in an increasingly competitive environment.

E-mail: This e-mail address is being protected from spam bots, you need JavaScript enabled to view it
Website: www.honeywellprocess.com
Last updated: 2016-03-24 15:42:11